General
● EN50298
● IEC68-2-30
● IEC68-2-11
● Anti-dust, waterproof. Protection degree: IP54. Comply with IEC 60529-1
● IEC60439-1, the maintenance and inspection can be done with power on
● Protection surface, shock proof!
Design
● compact structure
● all equipments can be installed before the cabinet
● the screw try to be of the same specification
● the vertical cross section increases by plugging strip bus
● the frame of the outgoing line functional unit is of the same
● the functional unit from of 4E to 12E is divided by a whole steel sheet
● flexible upper design, the protection degree is improved by adding the seal rings
Technical parameter
Item |
Unit |
Parameters |
Rated working voltage |
Ue |
AC380、AC660 |
Rated frequency |
HZ |
40-60 |
Rated current |
Horizontal busbar |
A |
1000-5000A |
Vertical busbar |
A |
850-2000A |
Rated short time withstand current |
Icw |
Max: 80KA/IS |
Rated withstand current (max) |
Ipk |
Max:176KA |
Rated insulation voltage |
Ui |
1000V |
Dimension |
mm |
2000(2200)*600(800、1000)*400(500、600、800、1000、1200)mm |
Functional unit modules basis |
|
1E=25mm |
Standard modulus |
|
4E-36E |
Max packing density |
|
80E |
|