Waterproof switch Metal Indicator Light Plastic Indicator Lamp LED Holder series Plastic push button ... Rocker switch&Panel USB socket& charger Toggle switch Micro switch Auto Switch Proximity Switch Overload circuit breaker AC socket Clip & Plug & Jack More electronics Terminal & Connector Cooling Fan Inverter Transformer HV Power Transmission

Tel:+86-577-61776977
      Mobi:+86-18066330701
Wechat:abbeycon18066330701
Skype:abbeycon827@outlook.com
Email:power@cnvcb.com

ZGS11 Combined Substation (American style)
Model
Z---------------------------------------combined      
G---------------------------------------HV 
S11-------------------------------------transformer
Z--------------------------------------design No.
□--------------------------------------rated capacity
 
General

       ZGS11 series of prefabricated substation is used in the 6~15KV ring net power supply, double or terminal power supply system as substation, distribution, measurement, compensation, controlling and protection devices. The inner of the prefabricated substation has not only the transformer, but also has 4-position load switch, 2-position load switch, backup protection fuse and plug-in fuse on the HV side. The low-voltage side can be equipped with electrical controller, distribution electric apparatus, and compensation device and electricity meter as per the user. It applies the transformer oil as the insulation and arc extinguishing media.
       ZGS11 series of prefabricated substation is developed on the combination of the most advanced technology and the actual state situation. The transformer is S9 type, and the whole products has the features of small size, easy installation, low noise, low loss, anti-theft, strong overload ability and safety, and therefore it is suitable for the new area, green belts, parks, railway station, docks, hotels, construction sites and airports.
       ZGS11 series of prefabricated substation meets the requirements of its components standard and GB/T 17467-1998 (HV and LV prefabricated substation) and the requirements of OZTC.536.009 (technology) and IEC61130:1995 (prefabricated substation).
 
 
Technical parameter

Serial No.
Item
Unit
Parameters
1
Rated voltage
Primary
KV
6~15
Secondary
KV
0.4,0.23
2
Rated capacity
 
KVA
100,125,160,200,250,
315,400,500,630,800,1000
3
No-load tap changer
 
 
±2*2.5%
4
Vector group
 
 
△/Yn11
5
Rated insulation level
Lightning impulse withstand voltage (full wave, peak)
KV
75
Power frequency withstand voltage 1min
KV
35
6
LV side power frequency withstand voltage, phase-phase and phase-earth (1min)
Main circuit
KV
2.5
Control and measuring circuit
KV
2.0
7
Noise level
 
dB
50
8
Protection degree
 
 
IP34
9
Cooling method
 
 
Oil immersed: ONAN