Waterproof switch Metal Indicator Light Plastic Indicator Lamp LED Holder series Plastic push button ... Rocker switch&Panel USB socket& charger Toggle switch Micro switch Auto Switch Proximity Switch Overload circuit breaker AC socket Clip & Plug & Jack More electronics Terminal & Connector Cooling Fan Inverter Transformer HV Power Transmission

Tel:+86-577-61776977
      Mobi:+86-18066330701
Wechat:abbeycon18066330701
Skype:abbeycon827@outlook.com
Email:power@cnvcb.com

HDXG-40.5KV Gas insulated metal-enclosed switchgear
●General

    HDXG-40.5kV gas insulated metal-enclosed switchgear, here called C-GIS for short, is a kind of high-quality product which Introduced overseas advanced technology and developed upon the particularity of China power grid. Part of its technical performance is superior to those of the same foreign products. It’s the first one through product appraisal, awarded model certificate and model use right by national professional department.
   It’s used in transmission and distribution of electricity system , to control 、measure and monitor when system works properly or out of order. Compared with other products, it has significant superiority in reliability, miniaturization and economy.
It conforms to National Standard GB11022, GB3906, DL404, GB1984, GB7674, GB50062, GB6162 and GB12022.
 
●Working Condition

a.Ambient air temperature: max temperature 45℃; average max daily temperature 35℃; min temperature -15℃;
b.Altitude: ≤3000m
c.Environment humidity: average daily value≤98%; average monthly value≤95%
d.Earthquake intensity ≤ 8 degree
e.Electromagnetic interference (EMI) of secondary system:≤ 1.6kv
 
Main technical parameter
 
Item
Unit
HDXG-40.5kV(C-GIS)
Rated voltage
KV(effective value)
Rated current
A
630/1250/1600/2000/2500
Rated frequency
HZ
50/60
Rated short time power frequency withstand voltage(Ud Imin)
phase to phase, phase to earth
KV(effective value )
95
Isolate break
KV(effective value )
110
Rated lightning surge withstand voltage
phase to phase, phase to earth
KV(peak value)
185
Isolate break
KV(peak value)
215
Rated short circuit breaking current
KA
25/31.5
Rated short circuit making current
KA
63/80
Rated short time withstand current
KA
23/31.5
Rated short time withstand uptime
S
4
Rated peak withstand current
KA
63/80
Shell protection grade
 
Gas-filled shell IP67, instrument room IP4X
Yearly leakage rate
%
≤0.2
Main loop resistance of each phase
 
≤200
Rated air pressure in gas tank(20℃ gage pressure)
Mpa
0.05
Rated max pressure in gas tank(20℃ gauge pressure)
Mpa
0.06
Rated min pressure in gas tank (20℃ gauge pressure)
Mpa
0.03
Mechanical life
Rated operating order
 
Off-0.3s, on/off-180s-on/off
Rated operating numbers
Times
30000(SIEMENS 3AHX)
Electrical durability
Rated short circuit breaking current
Times
50(SIEMENS 3AHX)
Breaking during rated current
Times
10000(SIEMENS 3AHX)
Rated control voltage
V
DCIIO/220
Weight
KG
800
Size(W*H*D)
mm
600*2650*400(600*2300*1400)