Waterproof switch Metal Indicator Light Plastic Indicator Lamp LED Holder series Plastic push button ... Rocker switch&Panel USB socket& charger Toggle switch Micro switch Auto Switch Proximity Switch Overload circuit breaker AC socket Clip & Plug & Jack More electronics Terminal & Connector Cooling Fan Inverter Transformer HV Power Transmission

Tel:+86-577-61776977
      Mobi:+86-18066330701
Wechat:abbeycon18066330701
Skype:abbeycon827@outlook.com
Email:power@cnvcb.com

Vacuum Load Switch

Description:

FZW33 12KV/24KV Outdoor AC vacuum disconnect load breaker is a new product adopts domestic existing mature load breaker switch production experience and overseas advanced technology to design and manufacture. The load breaker is composed of disconnect blade, vacuum interrupter and operation mechanism. vacuum extinguishing arc, there are merits as strong extinguishing arc ability, reliable performance, long lifetime, small volume, no explosive danger and no pollution to environment.

It accords with the standards of IEC62271-102 & GB/T3804:3.6~40.5kV High voltage switches, IEC60694 & GB/T11022: High voltage switch apparatus and control apparatus.

Techincal data:

N0.

Test Item

Unit

Data

1

Rated voltage

kV

12

24

2

Rated current

A

400/630

400/630

3

Rated frequency

Hz

50/60

50/60

4

Rated short-time withstand current

kA

20

20

5

Rated short-circuit duration

s

4

4

6

Rated active load breaking current

A

400/630

400/630

7

Rated loop breaking current

A

400/630

400/630

8

Rated cable charging current

A

12

12

9

5% rated active load breaking current

A

31.5

31.5

10

Rated short-circuit making current

kA

50

50

11

Main loop resistance

μΩ

≤100

≤100

12

power frequency withstand voltage against the earth, between phases

kV rms

40

65

13

power frequency withstand voltage against the isolating distance

kV rms

48

79

14

Lightning impulse withstand voltage against the earth, between phases (peak)

kV

75

125

15

Lightning impulse withstand voltage against the air gap(peak)

kV

85

145

16

Mechanical life

Times

10000

10000

17

Three phase closing asynchronous

ms

≤5

≤5

18

Main contact blade pressure

N

520

520

19

Distance between electric parts and phase to earth

mm

≧300

≧600

20

Rated operating force

N

≤300

≤300