GW4 40.5~252kV Two-column Disconnectors
Features:
l Outstanding performance and reliable operation
l Maintenance free due to its stable contact pressure and self-cleaning capability.
l High anticorrosion capability.
l Easy installation and adjustment.
Technical Data:
Item |
Unit |
Data |
Rated voltage |
kV |
40.5 |
126 |
145 |
252 |
Rated current |
A |
630, 1250 |
1250,2000 |
1250,2000 |
1250,2000,3150 |
Rated short-time withstands current(RMS), 3s |
kA |
31.5 |
31.5, 40 |
31.5, 40 |
31.5, 40,50 |
Rated withstands current (peak) |
kA |
80 |
80, 100 |
80, 100 |
80, 100, 125 |
Rated power frequency withstand voltage (RMS) |
To earth |
kV |
95 |
230 |
275(330) |
460 |
Breaks |
kV |
110 |
265 |
315(378) |
530 |
Rated lighting impulse withstand voltage (peak) |
To earth |
kV |
185 |
550 |
650(780) |
1050 |
Breaks |
kV |
215 |
630 |
750(900) |
1200 |
|