Description:
The HRC (high rupturing capacity) fuse−links are used to protect transformers, capacitor banks, cable and overhead lines against short−circuits. They protect
Switchgears from thermal and electromagnetic effects of heavy short−circuit currents by limiting the peak current values (cut−off characteristic) and interrupting the currents in several milliseconds.
Features:
− Rated voltage 3.6kV~40.5kV,Raed current up to 200A
− High rupturing capacity
− Short−circuit current limiting
− Low rated minimum breaking current (Imin)
− Low switching overvoltage (Um)
− Can be used with switch disconnector (it is fitted with a medium−size striker pin)
− Dimensions acc. to DIN and IEC Standards.
Techincal data:
Type |
Rated Voltage
kV |
Rated Current
A |
Breaking Capacity
kA |
øD
mm |
L
mm |
XRNT1/3.6 |
3.6 |
6.3,10,16,20,25,31.5,40 |
31.5 |
51 |
192 |
XRNT1/7.2 |
7.2 |
6.3,10,16,20,25,31.5,40,50,63 |
31.5 |
51 |
292 |
XRNT1/7.2 |
7.2 |
80,100,125,160 |
31.5 |
76 |
292 |
XRNT1/12 |
12 |
6.3,10,16,20,25,31.5,40 |
31.5 |
51 |
292 |
XRNT1/12 |
12 |
50,63,71,80,100 |
31.5 |
76 |
292 |
XRNT1/12 |
12 |
125 |
31.5 |
76 |
292 |
XRNT1/12 |
12 |
160,200 |
31.5 |
88 |
292 |
XRNT1/24 |
24 |
6.3,10,16,20,25,31.5,40 |
31.5 |
51 |
442 |
XRNT1/24 |
24 |
50,63,71,80,100 |
31.5 |
76 |
442 |
XRNT1/24 |
24 |
125 |
31.5 |
76 |
442 |
XRNT1/24 |
24 |
160 |
31.5 |
88 |
442 |
XRNT1/40.5 |
40.5 |
3.15,6.3,10,16,20,25 |
31.5 |
51 |
537 |
XRNT1/40.5 |
40.5 |
31.5,40 |
31.5 |
56 |
537 |
XRNT1/40.5 |
40.5 |
63 |
31.5 |
88 |
537 |
|
| |